NETIO PowerPDU 8QF is a PDU (Power Distribution Unit) with 8 power outputs (Type F/ "Schuko") controlled over a LAN network. By default, it is has been designed to fit into a 19" cabinet (1U) by fixed rack mount. Each output can be controlled independently. PowerPDU 8QF supports two channels for electrical metering: the PDU as whole (all outputs combined), and the first output as separate (Output 1). PowerPDU 8QF is equipped by DI (Digital Input). It offers additional possibilities of outputs control by connecting i.e. an external mechanical (dry contact) switch or temperature/ humidity sensor. With the NETIO T1 temperature/ humidity sensor, the defined output can be switched based on temperature (thermostat function).

 

The device’s WEB interface can be used to control the outputs, configure the Scheduler for each output, and so on. With the NETIO Cloud service, the outputs can be controlled from anywhere. The NETIO Cloud service is provided for a fee, features SSL security and its servers are located in Europe.

Open API enables integration into third-party systems using a wide range of protocols (JSON, Modbus/TCP, SNMP, MQTT, Telnet, ...). NETIO PowerPDU 8QS can be controlled from multimedia AV systems (Crestron, RTI, Control4, …)

 

  • Power input:              TypeF/ “Schuko” , fix cable 1.8m included, 110/230V (16A)
  • Power output:            8x TypeF/ “Schuko” (Total 16A; max 16A / output)
  • Output switching:     Each output can be switched on/off individually
  • Energy metering:      Yes (Total + Output 1)
  • Mobile app:               NETIO Mobile2 (Android)
  • Cloud service:          NETIO Cloud (with TLS security)
  • Industrial features:   Wide range of operating temperatures, PowerUp state, ZVS (Zero Voltage Switching)

 

Typical Application    

  1. AV remote restart of bricked devices
  2. IT data-centers for electricity distribution in a 19" rack (cabinet)
  3. Energy saving in meeting rooms (Scheduler switches equipment on/off at predefined time).
  4. Switching electrical outputs on/off with a mobile app
  5. Power output remotely switching by using NETIO Cloud
  6. Controlling the power (to TV sets, audio systems, lighting) from various AV systems in stores, smart homes, museums

>> NETIO usage examples

 

 

AV drivers for integration

NETIO products can be used together with plenty 3rd party software / hardware or cloud services.

  • Atlona
  • BrightSign media player (BrightAuthor]
  • Crestron (SIMPL blocks)
  • Control4
  • Cue
  • Domotz
  • ELAN
  • Elgato Stream Deck
  • HW group (Perseus platform)
  • Kramer (K-Config)
  • PIXILAB Blocks
  • LOXONE
  • RTI
  • SAVANT
  • SKAARHOJ
  • Utelogy
  • and many more

>> More about  Integration partners (3rd party)

 

Ask for a price or technical parameters

Documents to download

   
yt_icon_white
 
Video Flyer
 
pdf_ikona_white
Flyer PDF
 
pdf_ikona_white
Manual PDF (CE)

 

Remote restarting

Switch On / Off or Restart (short Off) each output using these methods:

  • From the device website
  • From the NETIO Cloud (web service).
  • From NETIO Mobile 2 (Mobile App) over LAN or NETIO Cloud (web service)
     
  • By external mechanical switch (dry contact) connected to DI input.
     
  • Using build in Week-Scheduler function you can define several On/Off intervals per each output.
  • With build in PING WatchDog function, you can restart any LAN device when not responding to PINGs from NETIO PDU (Device frozen)
  • With build in Power consumption WatchDog function, you can restart any device powered from metered NETIO PDU output. Device frozen / sleeping / IDLE mode is detected by power consumption drop for several time.
     
  • Using AV drivers you can control Outputs from many Audio Video SW (Crestron, Control4, Kramer, BrightSign, …)
     
  • There are plenty Open APIs (protocols) to control outputs / meter power consumption.
  • For example: JSON or XML over HTTP, SNMP v1 or v3, Modbus/TCP, MQTT, URL-API and others.
     
  • Using Windows executable PyNetio swtich / Toggle any NETIO output(s) from the Windows Desktop.
  • More: AN37 Outputs sequence started by Windows desktop icon (.bat file)

 

Power Measurement

NETIO PowerPDU 4C is small PDU with power measurement and IEC-320 outputs

NETIO PowerPDU 8QF measures electrical parameters – at the input for the device as a whole (All Outputs) as well as at the first output (Output 1). Measured values are displayed in the web administration interface and at the same time are accessible via Open API protocols. NETIO PowerPDU 8QS measures with accuracy better than 1%

Parameters measured for the whole device: 

  • Grid frequency [Hz]
  • Electrical voltage [V]
  • Total current [A]
  • Total power [W]
  • Overall TruePF [-])
  • Overall phase shift [°]
  • Total energy [kWh]
  • Total reverse energy [kWh]

Parameters measured for output 1: 

  • Current [A]
  • Power [W]
  • TruePF [-]
  • Phase shift [°]
  • Energy [Wh]
  • Reverse energy [Wh]

>> More about electrical metering

 

 

DI (Digital Input)

The DI (Digital Input) is green terminal block for connecting external mechanical switch (dry contact). Switching On/Off will be indicated on the device web interface.

Every single DI is realized as 3pin terminal block. There is 12V for powering external devices like smoke or movement detectors.

There is also 4bytes pulse counter on the DI (compatible with S0 pulses). 4 bytes counter can be used for reading consumption from an external meter. You can connect there any meter with pulse output (water meter, gas meter, 3phase electricity meter, …)

>> More about DI (Digital Input)

 

External sensors

One external sensor can be connected to each DI (Digital Input). Only original NETIO sensors are supported.
-    External Temperature sensor NETIO T1 (IP67 probe, 3m cable, -20℃ to +80 ℃)

-    External Temperature & Humidity sensor NETIO TH1 (PA probe, 3m cable, -20℃ to +80 ℃; 0 - 99 %RH)

Output switching based on DI state (sensor value).
With using the CR (Condition & Rules) can be local condition executed in the PDU to control one or more outputs based on DI current state or measured sensor value. Check the Condition & Rules in Glossary:.
>> More about DI (Digital Input)

 

Web_HTTPs

HTTPs

NETIO PDUs have implemented HTTPs security.
The HTTPs is supported both for the WEB interface and for Open API protocols (JSON, XML). A customer certificate can be used.

 

 

 

AV driversAV drivers icon

We can offer you drivers (integrated device support) for these AV (Audio Video) platforms:

  • Atlona
  • BrightSign
  • Control 4
  • Cue
  • Crestron
  • Domotz
  • ELAN
  • Elgato Stream Deck
  • HSYCO
  • Kramer
  • Loxone
  • Pixilab Blocks
  • Qsys
  • RTI
  • SAVANT
  • SKAARHOJ
  • Utelogy

These integrations / drivers can be free or paid. It's individual..
Drivers not tested by NETIO products, but provided by community are listed on wiki.netio-products.com

>> More about Integration partners (3rd party)


open_api

Open API (M2M protocols)

  • SNMP v1                               AN11, AN41
  • SNMP v3
  • MQTT-flex                             AN40
  • Telnet                                     AN10
  • Modbus/TCP                         AN27, AN22, AN37
  • JSON over HTTP                 AN21, AN30, AN42
  • XML over HTTP                    AN20, AN31
  • URL API (http get)                AN19, AN29
  • HTTP(s) Push JSON                      
  • HTTP(s) Push XML           

Regardless of the Open API used, the PowerPDU 8KB can always be controlled from its web interface and at the same time from the NETIO Cloud service. The customer can use the NETIO Cloud service and one Open API protocol at the same time.

 

Industrial product quality

 NETIO PDUs are made with quality in mind. Each unit includes a set of supporting functions to ensure reliability and long service life of the product in real-life conditions.
  • Open M2M API
  • Wide operating temperature range
  • PowerUp state – defined output state after power-up
  • PowerUp delay – outputs switched on after a delay
  • Input current up to 16A (output current max 10A / output)
  • Low internal consumption
  • Firmware upgradeable over the web, backwards compatibility
  • Very accurate electrical measurements, each unit is factory-calibrated
  • IOC – Independent Output Control
  • ZVS – Zero Voltage Switching

 

 

An important feature of NETIO PowerPDU 4C is ZCS (Zero Current Switching).

ZVS (Zero Voltage Switching)

 An important feature of the NETIO PowerPDU 8QB is ZVS (Zero Voltage Switching).

ZVS controls the exact time when the mechanical relay contacts close and open. The relay contacts switch the output on or off when the voltage crosses the zero level.  

  • In the long term, ZVS support reduces the product failure rate due to internal relay damage.
  • Since the relay switches when the sinusoidal voltage waveform crosses the zero level, negative effects of inrush current are significantly reduced.
  • The ZVS and PowerUp delay functions reduce the chance of circuit breakers tripping when power is restored after an outage.
  • ZVS extends the lifetime of connected equipment, especially in case of frequent on/off switching of devices that are not designed for that (such as switching power supplies).

>> Glossary: More about ZVS

 

 

 

The switching of outlets can be time-controlled by the Scheduler with a graphical interfaceScheduler (timed switching of individual outlets)

With the Scheduler (timer) function, each output can be individually switched on or off at specified times and days of week. The switching times are easily configured in a graphical interface.
 
  • Each output can have its own schedule
  • When a schedule is active, outputs can still be controlled with NETIO Cloud, the web interface and Open API
  • Scheduler functionality can be enabled/disabled (not edited) for each output from the NETIO Mobile 2 app.
     
  • Scheduler does not need an internet connection. However, a time source is needed – provided over the internet or, for example, by a local ADSL / WiFi router.
  • For special usage the Scheduler can be combined with PAB (Power Analyze Blocks):
    • Switching time is based on current sunrise/sunset based on your location
    • Whatever happend, defined output can be switched off on defined time (midnight for example).
    • Ask for more..

 >> More information about the Scheduler

 

Condition & RulesIcon_Condition-Rules

The NETIO Conditions (PAB & WatchDog) & Rules are preprogrammed in the device. It's great tool for special usage and applications.

Customer activate these functions in script based configuration. Using Condition & Rules it is possible to define reaction of the output(s) to the switching the button (DI input) or the reaction of defined output to the (non) response of PING WatchDog. NETIO Condition & Rules are supported by all NETIO devices manufactured after 2020 with the exception of PowerPDU 4C (supports LUA scripts).

Detailed description you can find on the wiki.netio-products.com, check the "NETIO Conditions & Rules: Local device scripting" part.

 

 

User can define output state after power restoring - PowerUp statePower-Up state

 For some applications, it is important to set the power output state immediately after the device is powered on (or the power is restored after a failure). With some machines it is important to avoid momentary switch-on or switch-off. This parameter therefore defines the behavior of the power output before the standard communication with a master system starts to work.
  • On
  • Off
  • LAST state restores the last state before the power was disconnected

Delay sequence when switching outputs on (PowerUp delay)

After a power outage, some electrical equipment can be switched on with a delay to avoid overloading and tripping circuit breakers. With the PowerPDU 8KB, use these parameters: “Power-Up state” = ON / LAST, and “Output PowerUp interval” = power-up delay before switching that particular output on.

>> Glossary: PowerUp state

 

 

WatchDog Ping + Power

PowerPDU 8QF is equipped with WatchDog PING (IP WatchDog) and WatchDog Power consumption (PAB).

  • WatchDog Ping continuously monitors whether a given process or a part of a system work as they should. If not, the WatchDog restarts the process. Can be used for all 8 outputs.
     
  • WatchDog Power is "Condition" & "Action" (PAB - Power Analysis Block & Rules) based autonomous system. It continuously monitors current (energy) of monitored device powered from any metered power output of NETIO PDU device.

>> Glossary: WatchDog PING (IP WatchDog)

>> Glossary: WatchDog - Power consumption (PAB)


 

NETIO Cloud

 The product can be connected to NETIO Cloud. Control 100 outputs from a single web screen!
NETIO Cloud is an ideal solution for remote control and restarting. It is accessible via any web browser: https://cloud.netio-products.com/
  • All devices produced by the NETIO products company can be connected to NETIO Cloud.
  • With every added device you receive free "Welcome Credit"
  • Remote PDU output control (from NETIO Mobile App or NETIO Cloud service website)
  • Multi-user feature for sharing devices in one company account
  • The User Rights (roles) can be defined for access control
  • PDU Connection Alert feature sends email notifications for PDU disconnections (connection or power failure).
  • Grouping and sub-group structure of PDUs (folders structure)
  • NETIO Mobile 2 App (Apple / Android) with user rights management
  • Open API (MQTT) to the company account of NETIO Cloud
  • The Historical Power Measurement Data can be downloaded
  • Remote firmware upgrade
  • 2 Factor Authentication
  • NETIO Cloud can be used in parallel with most of another Open API protocols.
  • Communication of PDU with the cloud service is secured (port 8883 - MQTTs - TLS).

The NETIO Cloud service is SaaS (online service). On-premise version of the cloud service is available for projects.

>> More about NETIO Cloud

 

Mobile app controlled power socketsMobile App

This device can controlled from mobile App NETIO Mobile 2 (Android & iOS).
  • LAN: NETIO Mobile 2 can control all outputs of devices within local LAN (WiFi).
  • Cloud: User account on the NETIO Cloud service can be connected to the mobile app.
 
You can do with mobile app
  • Control individual power outputs – switch ON, switch OFF, RESET
  • Read power consumption data (A, W, Wh), if this one output (device) supports energy metering

  • QR code for NETIO Mobile 2 AndroidQR code for NETIO Mobile 2 iOSActivate / deactivate the week Scheduler function per each output
  • Sorting of outputs within groups (by function or location)
  • Output grouping – default group per one device can be changed individualy
     
  • Group control - Switch the whole group of outputs On / Off
  • Group control - Activate / deactivate the week Scheduler function for each output in whole group
     
  • Change output / device name (visible in the mobile application only)
  • Add multiple devices to the mobile app.
  • LAN discover: Search your LAN/Wifi network for NETIO devices.

 

>> NETIO Mobile 2

 

 

General properties

  Switched
Power
Outputs
Metered
channels
LAN Web NETIO Cloud Lua scripts WatchDog Scheduler Mobile App Open API 19“ 1U
montage
Switching UL Certification
PowerPDU 4C (obsolete) 4x C13 4 2 Yes Yes Yes Ping Yes iOS + Android 15 protocols RM1 / RM2 
required
ZCS Yes
PowerPDU 4PS 4x C13 - 1 Yes Yes - Ping Yes iOS + Android 10 protocols RM1 / RM2 
​required
ZVS Yes
PowerPDU 4PB 4x NEMA 5-15R - 1 Yes Yes - Ping Yes iOS + Android 10 protocols RM1 / RM2 
​required
ZVS Yes
PowerPDU 4PV 4x powerCON - 1 Yes Yes - Ping Yes iOS + Android 10 protocols RM1 / RM2 
​required
ZVS Yes
PowerPDU 4KS 4x C13 4 1 Yes Yes - Ping + Power Yes iOS + Android 10 protocols RM1 / RM2 
​required
ZCS Yes
PowerPDU 4KB 4x NEMA 5-15R 4 1 Yes Yes - Ping + Power Yes iOS + Android 10 protocols RM1 / RM2 
​required
ZCS Yes
PowerPDU 8QS 8x C13 2 1 Yes Yes - Ping + Power Yes iOS + Android 10 protocols Yes ZVS Yes
PowerPDU 8QB 8x NEMA 5-15R 2 1 Yes Yes - Ping + Power Yes iOS + Android 10 protocols Yes ZVS Yes
PowerPDU 8QV 8x powerCON 2 1 Yes Yes - Ping + Power Yes iOS + Android 10 protocols Yes ZVS Yes
PowerPDU 8KS 8x C13 8 1 Yes Yes - Ping + Power Yes iOS + Android 10 protocols Yes ZCS Yes
PowerPDU 8KF 8x Type F/ "Schuko" 8 1 Yes Yes - Ping + Power Yes iOS + Android 10 protocols Yes ZCS No
PowerPDU 8QF 8x Type F/ "Schuko" 8 1 Yes Yes - Ping + Power Yes iOS + Android 10 protocols Yes ZVS No
PowerPDU 8KB 8x NEMA 5-15R 8 1 Yes Yes - Ping + Power Yes iOS + Android 10 protocols Yes ZCS Yes

 

Download

Flyer: 
Flyer CS
Flyer EN
Flyer DE
Manual: 
Manual CS
Manual EN
Manual DE
Quick Installation Guide: 
Guide CS
Guide EN
Guide DE

Photo and video

Product comparison

Ethernet: 
10/100Mbit
Lan ports: 
0
LAN ethernet switch: 
Yes
WiFi: 
Yes
WiFi AP mode: 
Yes
Blue Tooth 4.0 LE: 
Yes
Serial port (RS-232): 
No
DHCP: 
Yes
SNTP: 
Yes
SMTP (TLS): 
Yes
SSL: 
Yes
IPv6: 
Yes
VLAN: 
Yes
Syslog: 
Yes
SMS Alerts: 
Yes
Email alerts: 
Yes
Mobile App: 
No
Scheduler (Chytrý kalendář): 
Yes
IP Watchdog Hearbeat): 
No
Warranty 2: 
6 Months
Protection 2: 
IP30
Rack montage: 
None
Product dimensions: 
340 x 58 x 90 mm
Product weight: 
1,18 Kg
Shipping package: 
420 x 65 x 130 / 1350 g
HTTP: 
Yes
HTTPs: 
Yes
SNMP v1: 
Yes
SNMP v3: 
Yes
User certificates: 
Yes
XML: 
Yes
Modbus/TCP: 
Yes
Telnet/Kshell: 
Yes
CGI: 
Yes
MS Azure (MQTT): 
Yes
SIP VoIP: 
Yes
Power Output: 
4x DE (Type F - Schuko)
Power Input: 
230V AC
Power Output sockets: 
1
Power Input: 
Europlug - cable 1m
Power In max current: 
10A
Max one socket current: 
8A
Power fuse: 
External, mechanical
Current meter: 
No
Metered values: 
None
Energy meter: 
No
LUA: 
Yes
XML interface accessible in LUA: 
Yes
SNMP interface accessible in LUA: 
Yes
Web buttons accessible in LUA: 
Yes
CGI interface accessible in LUA: 
Yes
PING interface accessible in LUA: 
Yes
RS-232 accessible in LUA: 
No
Online demo IP address: 
http://powerpdu-8kf.netio-products.com
Symbol: 
Show download for mobile: 
1

Ask for a price or technical parameters